APPENDIX 1 - VACON® IO DATA DESCRIPTION
vacon • 209
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
11
11.4
Status Word bit support in VACON
®
AC drives
Table 210. FBFixedStatusWord bit support in different VACON
®
AC drives
11.5
Monitoring of Control & Status words in VACON
®
AC drives
The tables below describe where the control / status words can be read from different drives via
panel or PC-tool.
Table 211. Panel Tree for Control and Status Words
*Advanced Application only
For VACON
®
100 family, VACON
®
20 and VACON
®
20X/CP, VACON
®
Live PC tool is used for accessing
drive parameters. VACON
®
NCDrive PC tool is used with VACON
®
NXP drive.
NCDrive
•
View --> Monitoring
•
Type: Firmware
Bit
Function
VACON
®
100
family
VACON
®
NXP
VACON
®
20
VACON
®
20 X/CP
0
Ready
x
x
x
x
1
Run
x
x
x
x
2
Direction
x
x
x
x
3
Fault
x
x
x
x
4
Alarm
x
x
x
x
5
At reference
x
x
x
x
6
Zero speed
x
x
x
7
Flux ready
x
x
8
Info
x
9-15
Reserved
Signal
VACON
®
100 family
VACON
®
NXP
VACON
®
20
VACON
®
20 X/
CP
FBFixedControlWord
V2.12.1 (Low Word)
V1.24.1*
-
-
FBGeneralControlWord
V2.12.1 (High Word)
-
-
-
FBFixedStatusWord
V2.12.11 (Low Word)
V1.24.16*
V3.1
-
FBGeneralStatusWord
V2.12.11 (Low Word)
V1.24.3*
V3.2
-