Modbus TCP / Modbus UDP
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Table 37. Operation day counter
7.3.2.5.6.
R
ESETTABLE
OPERATION
DAY
COUNTER
This register holds the value for resettable control unit operating time counter (trip value). The
values are read only.
For resetting this counter see Chapter 7.3.2.2 "Clearing resettable counters".
NOTE!
The feature Resettable operation day counter does not work with VACON
®
20, VACON
®
20 X
or VACON
®
20 CP AC drives.
Resettable operation day counter as seconds
This counter in registers 40111
d
to 40112
d
holds the value of resettable operation days as seconds
in a 32-bit unsigned integer.
Table 38. Resettable operation days counter as seconds
Resettable operation day counter
This counter in registers 40101
d
to 40105
d
holds the value of operation days counter.
For compatibility with VACON
®
100 family internal Modbus TCP/UDP and the OPT-CI option board,
this counter is found from two different register areas: holding registers 40101
d
to 40105
d
and input
registers 30101
d
to 30105
d
.
Table 39. Resettable operation day counter
Holding register
addres
Input register
address
Purpose
40001
1
Years
40002
2
Days
40003
3
Hours
40004
4
Minutes
40005
5
Seconds
Address
Description
40111 High data
40112 Low data
Holds the counter value as seconds.
Holding register
addres
Input register
address
Purpose
40101
101
Years
40102
102
Days
40103
103
Hours
40104
104
Minutes
40105
105
Seconds