EtherNet/IP
vacon • 177
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
9
For the OPTE9, the revision of the object is 2.
9.2.2.4.1.
C
HANGES
FROM
REVISION
1
TO
REVISION
2
The attributes FaultCode and FaultDay were changed from 8 bit to 16 bit.
9.2.2.4.2.
C
LASS
A
TTRIBUTES
Class Attribute “Revision”
This attribute presents the revision of the Fault History Object which is implemented by the device.
The current revision is 2.
Class Attribute “Max Instance”
This attribute presents the maximum number of instances that can exist of the Fault History Object
in the device. The maximum value is 40.
Table 152. Fault history object
Class name
Fault history object
Class identifier
162
d
/ A2
h
Class
Attributes
Id
Access rule
Name
Datatype
Description
1
Get
Revision
UINT
Class revision (2)
2
Get
Max Instance
UINT
Maximum instance number
(40)
3
Get
Number of
Instances
UINT
Number of object instances.
Depends on drive type.
Class Ser-
vices
Id
Name
Description
1
Get_Attributes_All
Returns content of all (implemented)
attributes in the class.
5
Reset
Reset fault history
14
d
0E
h
Get_Attribute_Single
Used to read single attribute value.
Instance
Attributes
Id
Access rule
Name
Datatype
Description
1
Get
FaultCode
UINT
Fault code
2
Get
FaultID
UINT
Fault ID
3
Get
FaultYear
UINT
Fault date: Year
4
Get
FaultMonth
USINT
Fault date: Month
5
Get
FaultDay
UINT
Fault date: Day
6
Get
FaultMillisAfter
Midnight
UDINT
Fault date: Time, millisec-
onds after midnight
Instance
Services
Id
Name
Description
1
Get_Attributes_All
Returns content of all (implemented)
attributes in the instance
14
d
0E
h
Get_Attribute_Single
Used to read single attribute value
Summary of Contents for optea
Page 2: ......