Commissioning
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Subnet mask P1*
255
0…255
Subnet Mask Part 1
Subnet mask P2*
255
0…255
Subnet Mask Part 2
Subnet mask P3*
255
0…255
Subnet Mask Part 3
Subnet mask P4*
255
0…255
Subnet Mask Part 4
Default GW P1*
192
0…255
Default Gateway Part 1
Default GW P2*
168
0…255
Default Gateway Part 2
Default GW P3*
0
0…255
Default Gateway Part 3
Default GW P4*
1
0…255
Default Gateway Part 4
Speed/Duplex*
Autonegotia-
tion
Autoneg. (1),
10 HD (2),
10 FD (3),
100 HD (4),
100 FD (5)
Ethernet link speed/duplex selection. It is
recommend to use autonegotiation.
Sub menu: EtherNet/IP
EIP Output
Instance*
21
"20" (1),
"21" (2),
"23" (3),
"25" (4),
"101" (5),
"111" (6),
"128" (7),
"131" (8)
"151" (9),
"161" (10)
EtherNet/IP output assembly instance.
Shows the active output instance. The
instance is selected during the IO connec-
tion open request.
This parameter was removed in newer
firmware versions and replaced with mon-
itoring value.
EIP Input
Instance*
71
"70" (1),
"71" (2),
"73" (3),
"75" (4),
"107" (5),
"117" (6),
"127" (7),
"137" (8)
"157" (9),
"167" (10)
EtherNet/IP input assembly instance.
Shows the active input instance. The
instance is selected during the IO connec-
tion open request.
This parameter was removed in newer
firmware versions and replaced with mon-
itoring value.
EIP Product Code
Offset
0
0…99
Sub menu: Modbus
Modbus Unit Iden-
tifier*
255
1…247, 255
Modbus Unit Identifier. Used only with
Modbus UDP.
Sub menu: PROFINET IO
PNIO Name Of Sta-
tion
""
1...240 char
For Profinet IO only. Only visible in
VACON
®
100 family AC drives.
NOS Device ID
0
0…65535
Name Of Station device identification
number.
Not visible in VACON
®
100 family AC
drives.
Sub menu: SNTP
Name
Default
Range
Description