EtherNet/IP
vacon • 157
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
9
9.2.1.5
Ethernet Link Object, Class 0xF6
Ethernet Link Object provides interface to Ethernet link counters and attributes. With this object,
user can retrieve for example link speed.
Table 124. Ethernet Link Object
Class name
Ethernet Link Object
Class identifier
246
d
/ F6
h
Class
Attributes
Id
Access rule
Name
Datatype
Description
1
Get
Revision
UINT
Class revision (4)
2
Get
Max Instance
UINT
Maximum instance number
(2)
3
Get
Number of
Instances
UINT
Number of object instances
(2)
Class Ser-
vices
Id
Name
Description
1
Get_Attributes_All
Returns content of all (implemented)
attributes in the class.
14
d
0E
h
Get_Attribute_Single
Used to read single attribute value.
Instance
Attributes
Id
Access rule
Name
Datatype
Description
1
Get
Interface Speed
UDINT
Interface speed currently in
use
2
Get
Interface Flags
DWORD
Interface status flags
3
Get
Physical
Address
ARRAY of 6
USINTs
MAC layer address
4
Get
Interface Coun-
ters
STRUCT of
11 UDINTs
Interface counters. See
Table 126
5
Get
Media Counters
STRUCT of
12 UDINTs
Media specific counters.
See Table 127
7
Get
Interface Type
USINT
Type of interface: twisted
pair, fiber, internal, etc
8
Get
Interface State
USINT
Current state of the inter-
face: operational, disabled,
etc
9
Get/Set
Admin State
USINT
Administrative state: ena-
ble, disable
10
d
0A
h
Get
Interface Label
SHORT
STRING
Human readable identifica-
tion