Commissioning
vacon • 71
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
6.5.3
PROFINET in emulation mode
NX Mode:
•
PLC must use OPTCP GSDML.
•
Device id will be OPTCP's "1".
•
Vendor id will be OPTCP's "0x9500" instead of "0x01BA".
•
Device type text will be "OPTCP".
•
Telegrams will use FBSpeedReference/FBSpeedActual types instead of NSOLL_A/NIST_A.
•
Parameter channel used with Simatic PDM will not work in NX Mode.
•
In OPTCP Name Of Station can be set with NCIPConfig from the "node" field. This is not
supported, but there is separate parameter for Name Of Station in NCIPConfig when using
OPTEA or OPTE9 board.
•
OPTCP's Vendor PPO3, PPO4 and PPO6 telegrams are supported.
OPTCx Mode:
•
All same changes as in NX Mode.
•
FBDIN control word bits are as in OPTCP.
VACON
®
100 Mode:
•
PLC must use VACON
®
100 family GSDML.
•
Device id will be "1".
•
Device type text will be "VACON100".