PROFINET IO
vacon • 99
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
8
* 12 and 16 process data items are available in VACON
®
NXP AC Drive. See Chapter 16 "Appendix 6 -
Fieldbus option board communication".
When using these telegrams, the process data fields are communicated as 32-bit values, but when
using VACON
®
NX or VACON
®
20 family AC drives, the data is actually 16-bits and transferred in the
lower bytes.
* 32-bits. See Table 56
** See Chapter 8.3.1 "Choosing telegram type".
122
Vendor Telegram 2 + 5 Process Data
Vendor 2 + 5 PD
123
Vendor Telegram 2 + 6 Process Data
Vendor 2 + 6 PD
124
Vendor Telegram 2 + 7 Process Data
Vendor 2 + 7 PD
125
Vendor Telegram 2 + 8 Process Data
Vendor 2+ 8 PD
142
Vendor Telegram 2 + 12 Process Data *
Vendor 2 + 12 PD
143
Vendor Telegram 2 + 16 Process Data *
Vendor 2 + 16 PD
Table 56. Process data item definition when using Vendor telegram 2
Bytes
VACON
®
NX
VACON
®
20
VACON
®
100 family
1...2
16-bit Process data
16-bit Process data
Future release: 32-bit process data
3...4
Not used
Not used
Table 57. Vendor telegram 2 setpoint and actual data
Bytes
Setpoint
Actual value
1...2
FB FIXED CW
FB FIXED SW
3...4
FB GENERAL CW
FB GENERAL SW
5...6
FB SPEED REF
FB SPEED ACT
7...10
PDI1*
PDO1*
11...14
PDI2*
PDO2*
...
...
...
35...38
PDI8*
PDO8*
39...42
PDI9**
PDO9**
...
...
...
67...70
PDI16**
PDO16**
Table 55. Vendor telegram 2 and variants
Telegram No.
Telegram
Abbreviation