PROFINET IO
vacon • 101
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
8
When using these telegrams, the process data fields are communicated as 32-bit values, but when
using VACON
®
NX or VACON
®
20 family AC drives, the data is actually 16-bits and transferred in the
lower bytes.
* 32-bits. See Table 60
** See Chapter 8.3.1 "Choosing telegram type".
Control and Status Word monitoring values
When using this telegram, monitoring values contains values as shown in table below.
Table 60. Process data item definition when using Vendor telegram 3
Bytes
VACON
®
NX
VACON
®
20 / 20 X
VACON
®
100 family
1...2
16-bit Process
data
16-bit Process data
Future release: 32-bit process data
3...4
Not used
Not used
Table 61. Vendor telegram 3 setpoint and actual data
Bytes
Setpoint
Actual value
1...2
STW1
ZSW1
3...4
FB GENERAL CW
FB GENERAL SW
5...6
NSOLL_A
NIST_A
7...10
PDI1*
PDO1*
11...14
PDI2*
PDO2*
...
...
...
35...38
PDI8*
PDO8*
39...42
PDI9**
PDO9**
...
...
...
67...70
PDI16**
PDO16**
Table 62. Control and Status Word monitoring values
Name
Value
Drive CW
FBFixedControlWord
Drive SW
FBFixedStatusWord
Protocol CW
STW1
Protocol SW
ZSW1