Output Module Reference Data
E1/2048 kHz Output Module
188
SSU-2000 User’s Guide
12713020-002-2 Revision D – April 2004
SSU+>al 2a10
2002-07-04T10:25:31 ID: SSU2000 Name: SSU
Output #
Alarm
Status
Level(*=Elev)
Ports
------- ---- ------------------ --------------- ------------- ---------
1A06
(00) Hdw Config
Ok
Major
1A06
(01) Configuration
Ok
Major
1A06
(02) Clk-A
Ok
Major
1A06
(03) Clk-B
Ok
Major
1A06
(04) Clk-C
Ok
Major
1A06
(05) Clk-D
Ok
Major
1A06
(06) Clk Selected
Ok
Major
1A06
(07) VCXO
Ok
Major
1A06
(08) PLL
Ok
Major
1A06
(09) Sync
Ok
Major
1A06
(10) Squelch
Ok
Major
1A06
(11) PortFlt
Ok
Major
SSU->
Provisioning the Squelch Parameter
To view or provision the squelch using ICS commands, see
To provision the squelch using TL1 commands, see
Bypass Clock (Clock C) Alarms
The SSU-2000 has many configuration options. In order for the system to generate
the CLK-C used by the E1/2048 kHz Output module, you must install one of the
following Input modules and connect an input signal to the module: DS1, E1, or CC.
If the SSU-2000 has only GPS Input module(s), then set the Bypass mode to OFF
to prevent the Output modules from generating the CLK-C alarm (alarm 4).
Output Fault Handling
When an output fault occurs, a port fault alarm occurs. Fault recovery is automatic;
when the fault is no longer present, normal operation continues. To prevent
“bouncing,” or reporting errors continuously, the module increments an error counter
each time a port fault occurs. If the error count exceeds a preset threshold, then the
faulty port is disabled. You must disable and then enable the port using software
commands to return it to normal service. The error counter automatically resets
when there are no errors in 24 hours.
Note:
For ports set to E1, the frame mode is always CAS, the CRC is
always enabled, and the SSM is sent to all five bit positions (4 through 8).
You cannot change these settings.
Summary of Contents for SDU-2000
Page 12: ...12 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 18: ...18 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 390: ...SNMP Protocol 390 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 420: ...I O Connector Grounding 420 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...