Commissioning
Commissioning Tests
108
SSU-2000 User’s Guide
12713020-002-2 Revision D – April 2004
6. Replace the fuse to restore Power A to the unit.
7. Verify that the alarm clears, is reported and logged.
Testing the CRITICAL Alarms
To test the CRITICAL alarm relay closures and software:
1. Set the Power A alarm level to CRITICAL:
ICS format:
ALARM 1A02
CRITICAL
TL1 format:
SET-PRMTR-ALARM::S1A2:::02,CRITICAL;
2. Remove Power A input by removing the A-bus fuse (or the fuse that supplies
Power A).
3. Verify that the CRITICAL alarm indicator is ON.
4. Verify that the CRITICAL alarm is reported to the communications terminal.
5. Verify that a CRITICAL alarm was logged in the event log:
ICS format:
EVENT ALARM
TL1 format:
RTRV-EVENT::S1A2;
6. Replace the fuse to restore Power A to the unit.
7. Verify that the alarm clears, is reported and logged.
8. Type
ALARM
and press
Enter
to restore Power A to the original alarm level.
Testing the Reference Signals and Selection
To test the reference signals and selection:
1. Type
INPUT
to verify each input signal is present with no alarms. Each reference
input will be listed by module position and port number, status, phase A and B
readings, input PQL, signal alarms, and MTIE alarms.
The status should be
OK
and the Priority Quality Level (PQL) should indicate the
received Sync Status Message (SSM) level or the provisioned value. The phase
values will be dependent on the received signal. The signal alarms should be
/////
(no alarms present, F indicates an alarm) and the MTIE alarms should all be
OK
.
2. Type
REF
and press
Enter
to determine the current selection of input reference
signal. Disconnect this input signal and verify a Loss Of Signal (LOS) is reported
for the input, and the unit selects an alternate input for the reference signal.
Summary of Contents for SDU-2000
Page 12: ...12 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 18: ...18 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 390: ...SNMP Protocol 390 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 420: ...I O Connector Grounding 420 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...