Hardware Configuration Guide
Configuring a Subtending SSU
230
SSU-2000 User’s Guide
12713020-002-2 Revision D – April 2004
Changing to Subtending SSU Mode
To change an SSU-2000 to a Subtending SSU, you must verify that the proper
hardware is present, and you must install the appropriate software. The minimum
software versions for the modules is listed in
.
Required Hardware
The Subtending SSU mode
requires
the following modules in the shelf:
CC Input module
CC Output module
All other available modules can be used in the Subtending SSU mode. The shelf
must contain the appropriate Clock module(s), Communications module, and Input
and Output modules.
Table 9-1. Minimum Software Versions for Subtending Operation
Module
Minimum Revision Level
Communications:
Basic Load
Basic + NTP
Basic + SNMP
Basic + NTP + SNMP
D.00
B.00
B.00
B.00
Clock (ST2 or ST3E)
C.00
Composite Clock Input
A.00
Composite Clock Output
PLD: B.00
S/W: B.00
Summary of Contents for SDU-2000
Page 12: ...12 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 18: ...18 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 390: ...SNMP Protocol 390 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 420: ...I O Connector Grounding 420 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...