12713020-002-2 Revision D – April 2004
SSU-2000 User’s Guide 311
TL1 Command Interface
SET-PRMTR-OUTPUT:[tid]:[aid]
:ctag::[pstate],[mode],
[level],[bypass],[zs],[crc],
[len],[bit];
Valid aid code:
ALL
,
SxA[y[-z]]
This command sets the output port parameters.
where:
pstate
= enabled or disabled [ON|OFF]
mode
= signal mode [ESF|D4|CCS|CAS]
level
= outputs are turned on [WARM |ACQ |LOCK]
For framed outputs:
zs
= zero suppression
crc
= error checking [ON|OFF]
len
= line length setting of [133|266|399|533|655] feet for
DS1 outputs
bit
= ssm bit [4| through [8] for E1 sync status messages
bypass
= allow Clock C selection [ON|OFF]
Setting the status for a module (no port –z) sets all ports
[ON|OFF]. Empty fields leave parameters unchanged.
SET-PRMTR-PBO:[tid]::ctag::
pbo_mode;
Valid aid code: none
The pbo_mode is [DIS| EVT| REP| NONE].
DIS
disables the phase buildout (PBO) function.
EVT
enables the PBO function. The PBO event is
displayed and stored in the COMM module event buffer.
REP
enables the PBO function. The PBO event is
displayed, but the event is not stored in the COMM
module event buffer.
NONE
enables the PBO function. The PBO event is neither
displayed nor stored in the COMM module event buffer.
SET-PRMTR-SETUP:[tid]:[aid]:
ctag::[factory| user|save];
Valid aid code:
ALL
,
SxA[y[-z]]
This command sets or saves the configuration of the specified
module.
Factory
restores the module configuration to factory defaults.
Any time the configuration has changed from the factory
configuration, these configurations become the current
configurations.
Save
stores the current configuration.
The
user
parameter reloads the previously saved configuration.
SET-PRMTR-SNMP-MODE:[tid]::
ctag::[mode], [trap_filter];
Valid aid code: None
This command sets the SNMP mode and trap filter parameters.
Values for
mode
are as follows:
ENA
Enables SNMP operation in the system
DIS
Disables SNMP operation in the system
Values for
trap_filter
are as follows:
ALM
Only alarms cause Traps to be transmitted
ALL
All events and alarms cause the transmission of Traps
Empty fields leave parameters unchanged.
Table B-6. TL1 Set Commands (Continued)
Command
Description
Summary of Contents for SDU-2000
Page 12: ...12 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 18: ...18 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 390: ...SNMP Protocol 390 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 420: ...I O Connector Grounding 420 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...