12713020-002-2 Revision D – April 2004
SSU-2000 User’s Guide 217
Output Module Reference Data
Line Retiming Unit (LRU)
Provisioning the LRM
The following information provides examples of how to use ICS and TL1 commands
to provision an LRM in an SSU-2000. Refer to
, on page 315, for details on ICS and TL1
commands.
Examples
The following ICS commands enable port 2 on an LRM in slot 8 of shelf 3, set the
line build-out to 399 feet, and set the slip error threshold to 6:
LRM 3A8-2 ENABLE
then press
Enter
LRM 3A8-2 LBO 399
then press
Enter
LRM 3A8-2 SLIP 6
then press
Enter
SET-PRMTR-LRM::S3A8-2:::ON,399,6,,;
The following ICS commands enable port 3 of an LRM in slot 11 of shelf 2 and
enables a FAULT strategy,:
LRM 2A11-3 FLT AIS
then press
Enter
SET-PRMTR-LRM::S2A11-3:::ON,,,,,AIS;
The following ICS commands set the circuit ID of port 4 on an LRM in slot 7 of shelf
1 to 1A7-4:
LRM 1A7-4 CID 1A7-4
then press
Enter
SET-PRMTR-LRMCID::S1A7-4:::1A7-4;
Alarms and Events
The LRM generates the alarms and events listed in
,
respectively.