2-30
1010BXFM-3
Section 2
2.4.10 THE EMPTY PIPE SET MENU
The computer performs the MTYmatic routine automatically during its Initial Make-up to
establish a standard setting for the Empty Pipe alarm. The Empty Pipe Set option list allows
you to re-invoke MTYmatic, use an Actual MTY routine (if application conditions allow you to
empty and refill the pipe) or use the Set Empty routine to set the empty pipe threshold by
direct numeric entry.
How to Use the Actual MTY Command
If application conditions allow you to empty and refill the pipe, then you should perform the
Actual Empty procedure. This is the recommended way to define the empty pipe threshold.
WARNING: NEVER perform this procedure when the pipe cannot be emptied.
To perform the Actual MTY Procedure:
To access the [Empty Pipe Set] option list press
To move the cursor to [Actual MTY] press then press
Empty the pipe completely, then press
.
appears on
the menu prompt line.
Refill the pipe completely, then press
How to Use the MTYmatic Command
You can repeat MTYmatic (performed during the Initial Makeup) to correct an inaccurate
actual MTY setting if conditions did not allow you to complete the Actual Empty procedure.
NOTE: Only use the MTYmatic procedure when the pipe is full.
To start MTYmatic:
To access the [Empty Pipe Set] option list press
Move the cursor next to [MTYmatic] by pressing
To invoke MTYmatic press
ENT
[Empty Pipe Press Enter]
ENT
ENT
ENT
appears on the menu prompt line.
[Fill Pipe Press Enter]
After the computer completes its Initial Makeup command, the [Install Complete?] option list
changes to:
If you want to redo the Initial Makeup, move cursor to [New Makeup], then press .
This resets the option list. You can now repeat the install routine described previously.
ENT
Install Completed? Yes
New Makeup
Summary of Contents for SITRANS FUH1010PVX
Page 2: ......
Page 6: ......
Page 14: ......
Page 28: ......
Page 130: ......
Page 186: ......
Page 187: ...Siemens Hardware ...
Page 188: ......
Page 189: ...Siemens Hardware ...
Page 190: ......
Page 191: ...Siemens Hardware ...
Page 192: ......
Page 193: ...Siemens Hardware ...
Page 194: ......
Page 195: ...Siemens Hardware ...
Page 196: ...1010N 5 7 INSTALLATION DRAWING ANALOG INPUT MODULE 21614 C ...
Page 201: ...1011HNS 8 TRANSDUCER PART NUMBER L H W SIZE C D SIZE A B 21614 C Siemens Hardware ...
Page 202: ......
Page 203: ...Siemens Hardware ...
Page 204: ......
Page 206: ......
Page 214: ......
Page 225: ...Siemens Hardware ...