Acknowledge events
Table 4-70
Acknowledge events
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
6248
Unsigned / 2
Acknowledge
mode
Mode to acknowledge
active events.
1
● 0: Manual alarm
acknowledge
(indication will remain
even when event is
gone)
● 1: Automatic
acknowledge
(indication will
disappear when
event is gone)
Read /
write
6294
Unsigned / 2
Alarm acknowl‐
edgement
Command to acknowl‐
edge a specific alarm
item in manual ac‐
knowledge mode.
Enter ID related to the
-
-
Write on‐
ly
Assign alarm class
Table 4-71
Assign alarm class
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
6328
Unsigned / 2
Transmitter
temp. too high
Defines the mapping of
this event to an alarm
class respective NA‐
MUR status signal.
1
● 1: Process alarm
(PA) resp. Out of
specification.
● 4: Maintenance alarm
(MA) resp. Failure.
Read /
write
6329
Unsigned / 2
Transmitter
temp. too low
Defines the mapping of
this event to an alarm
class respective NA‐
MUR status signal.
1
● 1: Process alarm
(PA) resp. Out of
specification.
● 4: Maintenance alarm
(MA) resp. Failure.
Read /
write
MODBUS commands
4.10 Modbus holding registers tables
FCT030 Modbus (From firmware 4.0)
142
Function Manual, 06/2018, A5E39931813-AB