Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units register)
Value range /
Setting options
Access
level
9199
Unsigned / 2
NAMUR status
signals
Bit encoded selection
of NAMUR status sig‐
nals which impacts the
status output.
Applicable if Status
mode = 0. NAMUR sta‐
tus is derived from
Alarm class (9158).
0
● Bit 0: Out of
specification (PA,
PW)
● Bit 1: Failure (MA)
● Bit 2: Maintenance
required (MR, MD)
● Bit 3: Function check
(FC)
Read /
write
9142
Unsigned / 4
Alarm items 1
Bit encoded selection
of alarm items that im‐
pact the output. Mainly
sensor alarms. See
if Status mode = 1.
0
Read /
write
9144
Unsigned / 4
Alarm items 2
Bit encoded selection
of alarm items that im‐
pact the output. Mainly
sensor alarms. See
if Status mode = 1.
0
Read /
write
9148
Unsigned / 4
Alarm items 4
Bit encoded selection
of alarm items that im‐
pact the output. See
if Status mode = 1.
0
Read /
write
9150
Unsigned / 4
Alarm items 5
Bit encoded selection
of alarm items that im‐
pact the output. See
if Status mode = 1.
0
Read /
write
9156
Unsigned / 4
Alarm items 8
Bit encoded selection
of alarm items that im‐
pact the output. See
if Status mode = 1.
0
Read /
write
10156
Unsigned / 4
Alarm items 9
Bit encoded selection
of alarm items that im‐
pact the output. See
if Status mode = 1.
0
Read /
write
MODBUS commands
4.10 Modbus holding registers tables
FCT030 Modbus (From firmware 4.0)
102
Function Manual, 06/2018, A5E39931813-AB