Channel 3 analog input settings
Table 4-41
Channel 3 analog input settings
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units register)
Value range /
Setting options
Access
level
10522
Unsigned / 2
Current mode
Mode of current output. 0
● 0: 4-20 mA (3.5)
3.8-20.5 (22.6)
NAMUR
● 1: 4-20 mA (3.75)
4.0-20.8 (22.6) US
● 2: 4-20 mA (2.0)
4.0-20.5 (22.0)
● 3: 4-20 mA (2.0)
4.0-24.0 (25.0)
● 4: 0-20 mA (0.0)
0.0-20.5 (22.0)
● 5: 0-20 mA (0.0)
0.0-24.0 (25.0)
Read /
write
10531
Float / 4
Upper range
value tempera‐
ture
Upper medium temper‐
ature value that is map‐
ped to the upper nomi‐
nal range boundary se‐
lected by Current mode
(10522). Applicable if
Process value (10523)
= 1.
Max. medium
temperature
[°C]
(7700)
-
Read /
write
10533
Float / 4
Lower range
value tempera‐
ture
Lower medium temper‐
ature value that is map‐
ped to the lower nomi‐
nal range boundary se‐
lected by Current mode
(10522). Applicable if
Process value (10523)
= 1.
Min. medium
temperature
[°C]
(7700)
-
Read /
write
10537
Float / 4
Upper range
value density
Upper process density
value that is mapped to
the upper nominal
range boundary selec‐
ted by Current mode
(10522). Applicable if
Process value (10523)
= 2.
1600.0
[kg/m3]
(7600)
-
Read /
write
10539
Float / 4
Lower range
value density
Lower process density
value that is mapped to
the lower nominal
range boundary selec‐
ted by Current mode
(10522). Applicable if
Process value (10523)
= 2.
600.0
[kg/m3]
(7600)
-
Read /
write
MODBUS commands
4.10 Modbus holding registers tables
FCT030 Modbus (From firmware 4.0)
106
Function Manual, 06/2018, A5E39931813-AB