Commissioning
4.4 Commissioning with the BOP-2
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
66
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
4.4.3
Basic commissioning
Menu
Remark
OK
6(783
Set all of the parameters of the menu "SETUP".
In the BOP-2, select the menu "SETUP".
OK
5(6(7
Select reset if you wish to reset all parameters to the factory setting before the basic
commissioning. NO → YES → OK
Select the motor control mode. The most important control modes are:
VF LIN
V/f control with linear characteristic
VF QUAD
V/f control with square law characteristic
SPD N EN
Closed-loop speed control (vector control)
OK
S
&75/02'
TRQ N EN
Closed-loop torque control
OK
S
(8586$
②
Standard: IEC or NEMA
OK
S
02792/7
①
Voltage
OK
S
027&855
③
Current
OK
S
02732:
④
Power IEC standard (kW)
⑤
power NEMA standard (HP)
OK
S
027530
⑥
Rated speed
2.0 HP
3.55-3.55
2.05-2.05
84.5%
84.5%
86.5%
NOM.EFF
K
A
V
380 - 420
660 - 725
CL
IP55
E0807/0496382_02 003
IMB3
UNIREX-N3
40°C
Tamb
Th.Cl. 155(F)
25 kg
Design A
TEFC
MG1-12
NEMA
SF 1.15 CONT
60Hz:
Intervall: 4000hrs
IEC/EN 60034 100L
3~Mot. 1LE10011AC434AA0
6206-2ZC3
6206-2ZC3
Bearing
DE
NE
11g
15g
D-91056 Erlangen
-20°C
2.0 HP
3.55-3.55
2.05-2.05
84.5%
84.5%
86.5%
NOM.EFF
K
A
V
380 - 420
660 - 725
CL
IP55
E0807/0496382_02 003
IMB3
UNIREX-N3
40°C
Tamb
Th.Cl. 155(F)
25 kg
Design A
TEFC
MG1-12
NEMA
SF 1.15 CONT
60Hz:
Intervall: 4000hrs
IEC/EN 60034 100L
3~Mot. 1LE10011AC434AA0
6206-2ZC3
6206-2ZC3
Bearing
DE
NE
11g
15g
D-91056 Erlangen
-20°C
Y
400
460
690
V
970
970
1175
rpm
0.73
0.73
0.69
PF
3.15
3.5
2.05
A
kW
Hz
50
60
50
1.5
1.5
1.5
Motor data on the rating plate
OK
S
027,'
We recommend the setting STIL ROT (Identify motor data at standstill and with the motor
rotating).
If the motor cannot rotate freely, e.g. where travel is mechanically limited, select the setting
STILL (Identify motor data at standstill).
OK
S
0$&3$5
Select the configuration for the inputs and outputs, as well as the correct fieldbus for your
application. The predefined configurations can be found in the section titled Selecting the
interface assignments (Page 48).
OK
S
0,1530
Minimum motor speed.
OK
S
5$0383
Motor ramp-up time.
OK
S
5$03':1
Motor ramp-down time.
ESC
OK
),1,6+
Confirm that the basic commissioning has been completed (Parameter p3900):
NO → YES → OK