Technical data
10.2 Technical data, Power Modules
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
315
Table 10- 14 PM240 frame size D, 3-ph. 380 V AC… 480 V, ± 10 %
Order number
with filter
without filter
6SL3224-0BE31-5AA0
6SL3224-0BE31-5UA0
6SL3224-0BE31-8AA0
6SL3224-0BE31-8UA0
6SL3224-0BE32-2AA0
6SL3224-0BE32-2UA0
Values based on Low Overload
● LO power
● LO input current
● LO output current
18.5 kW
46 A
38 A
22 kW
53 A
45 A
30 kW
72 A
60 A
Values based on High Overload
● HO power
● HO input current
● HO output current
15 kW
40 A
32 A
18.5 kW
46 A
38 A
22 kW
56 A
45 A
General values
● Power loss
● Fuse
● Cooling air requirement
● Cable cross-section for line and
motor connection
● Torque for line and motor and
motor connection
● Weight with filter
● Weight without filter
0.44 kW
50 A
55 l/s
10 … 35 mm
2
6 Nm
16 kg
13 kg
0.55 kW
63 A
55 l/s
10 … 35 mm
2
6 Nm
16 kg
13 kg
0.72 kW
80 A
55 l/s
10 … 35 mm
2
6 Nm
16 kg
13 kg
Table 10- 15 PM240 frame size E, 3-ph. 380 V AC… 480 V, ± 10 %
Order number
with filter
without filter
6SL3224-0BE33-0AA0
6SL3224-0BE33-0UA0
6SL3224-0BE33-7AA0
6SL3224-0BE33-7UA0
Values based on Low Overload
● LO power
● LO input current
● LO output current
37 kW
88 A
75 A
45 kW
105 A
90 A
Values based on High Overload
● HO power
● HO input current
● HO output current
30 kW
73 A
60 A
37 kW
90 A
75 A
General values
● Power loss
● Fuse
● Cooling air requirement
● Cable cross-section for line and
motor connection
● Torque for line and motor and
motor connection
● Weight with filter
● Weight without filter
1.04 kW
100 A
110 l/s
25 … 35 mm
2
6 Nm
23 kg
16 kg
1.2 kW
125 A
110 l/s
25 … 35 mm
2
6 Nm
23 kg
16 kg
Summary of Contents for SINAMICS G120 CU230P-2
Page 2: ......