Functions
7.9 Application-specific functions
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
260
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
p0757.3 = 0 / p0758.3 = 0
Set lower value of the scaling characteristic
p0759.3 = 100 / p0760.3 =
100
Set upper value of the scaling characteristic
p31026.2 = 755.1
Temperature actual value 3 via temperature sensor with
current output (0 mA … 20 mA) via analog input 1
p0756.1 = 2
Select analog input type (current input 0 … 20 mA)
p0757.1 = 0 / p0758.1 = 0
Set lower value of the scaling characteristic (0 mA ≙ 0 °C)
p0759.1 = 20 / p0760.1 = 100 Set upper value of the scaling characteristic (20 mA ≙ 100 %)
p31025 = 722.4
Changeover from day to night via digital input 4
You will find more information about this multi-zone control in the parameter list and in
(function diagram 7972 of the List Manual).