Installing
3.3 Installing Power Module
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
33
Dimensions and drilling patterns for the PM250 Power Modules
&RROLQJ
DLU
7KHUPDO
GLVVLSDWLRQ
:LGWK
+H
LJ
K
W
'HSWK
WR
S
ER
WW
RP
ODWHUDO
ODWHUDO
'HSWK
E
D
)6&)6)
)6&)6)
)6&)6)
)6&)6)
F
&RQWURO8QLW
Figure 3-3
PM250 drilling pattern
Table 3- 3
PM250, IP20 dimensions
Dimensions (mm)
Clearances (mm)
Frame size
Height
Width
Depth
a
b
c
top
bottom
lateral
FSC
334
189
185
323
167
--
125
125
50*
FSD without filter
419
275
204
325
235
11
300
300
0
FSD with filter, Class A
512
275
204
419
235
11
300
300
0
FSE without filter
499
275
204
405
235
11
300
300
0
FSE with filter, Class A
635
275
204
541
235
11
300
300
0
FSF without filter
634
350
316
598
300
11
350
350
0
FSF with filter, Class A
934
350
316
899
300
11
350
350
0
Fixing:
FSB: M4 screws, 2.5 Nm / 22 lbf .in FSD/FSE:
M6 screws, 6 Nm/53 lbf .in
FSC: M5 screws, 2.5 Nm / 22 lbf .in FSF/: M8
screws, 13 Nm / 115 lbf .in
*) up to 40 °C without any lateral clearance
Summary of Contents for SINAMICS G120 CU230P-2
Page 2: ......