Configuring the fieldbus
6.3 Communication over CANopen
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
177
6.3.4.1
Free objects
You can interconnect any process data objects of the received and transmit buffer using
receive and transmit double words.
●
Scaling the process data of the free objects:
–
16 bit (word): 4000hex ≙100 %
–
For temperature values: 16 bit (word): 4000hex ≙ 100 °C
OD index
(hex)
Description
Data type
per PZD
Default
values
Can be
read/
written to
5800 to 580F 16 freely-interconnectable receive process data Integer16
0
R/W
5810 to 581F 16 freely-interconnectable transmit process
data
Integer16
0
R