Configuring the fieldbus
6.3 Communication over CANopen
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
173
OD
Index
(hex)
Sub-
Index
(hex)
Name of the object
SINAMICS
parameters
Data type
Predefined
connection
set
Can be
read/
written to
1607
Receive PDO 8 mapping parameter
0
Number of mapped application objects in PDO
Unsigned8
0
R
1
PDO mapping for the first application object to be
mapped
p8717.0
Unsigned32 0
R/W
2
PDO mapping for the second application object to
be mapped
p8717.1
Unsigned32 0
R/W
3
PDO mapping for the third application object to be
mapped
p8717.2
Unsigned32 0
R/W
4
PDO mapping for the fourth application object to
be mapped
p8717.3
Unsigned32 0
R/W
TPDO configuration objects
The following tables list the communication and mapping parameters together with the
indices for the individual TPDO configuration objects. The configuration objects are
established via SDO.
Table 6- 51 TPDO configuration objects - communication parameters
OD
Index
(hex)
Sub-
Index
(hex)
Object name
SINAMICS
parameters
Data type
Predefined
connection set
Can be
read/
written to
1800
Transmit PDO 1 communication parameter
0
Largest subindex supported
Unsigned8
5
R
1
COB ID used by PDO
p8720.0
Unsigned32
180 hex + node ID
R/W
2
Transmission type
p8720.1
Unsigned8
FE hex
R/W
3
Inhibit time
p8720.2
Unsigned16
0
R/W
4
Reserved
p8720.3
Unsigned8
---
R/W
5
Event timer
p8720.4
Unsigned16
0
R/W
1801
Transmit PDO 2 communication parameter
0
Largest subindex supported
Unsigned8
5
R
1
COB ID used by PDO
p8721.0
Unsigned32
280 hex + node ID
R/W
2
Transmission type
p8721.1
Unsigned8
FE hex
R/W
3
Inhibit time
p8721.2
Unsigned16
0
R/W
4
Reserved
p8721.3
Unsigned8
---
R/W
5
Event timer
p8721.4
Unsigned16
0
R/W
1802
Transmit PDO 3 communication parameter
0
Largest subindex supported
Unsigned8
5
R
1
COB ID used by PDO
p8722.0
Unsigned32
C000 06DF hex
R/W
2
Transmission type
p8722.1
Unsigned8
FE hex
R/W
3
Inhibit time
p8722.2
Unsigned16
0
R/W
4
Reserved
p8722.3
Unsigned8
---
R/W
5
Event timer
p8722.4
Unsigned16
0
R/W
Summary of Contents for SINAMICS G120 CU230P-2