Functions
7.6 Motor control
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
204
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
0
7.6
Motor control
For induction motors, there are two different open-loop control or closed-loop control
techniques:
●
Open-loop control with V/f-characteristic (V/f control)
●
Field-oriented control (vector control)
Criteria for selecting either V/f control or vector control
V/f control is perfectly suitable for almost any application in which the speed of induction
motors is to be changed. Examples of typical applications for V/f control include:
●
Pumps
●
Fans
●
Compressors
●
Horizontal conveyors
Commissioning vector control takes more time than when commissioning V/f control. When
compared to V/f control, vector control offers the following advantages:
●
The speed is more stable for motor load changes.
●
Shorter accelerating times when the setpoint changes.
●
Acceleration and braking are possible with an adjustable maximum torque.
●
Improved protection of the motor and the driven machine as a result of the adjustable
torque limiting.
●
The full torque is possible at standstill.
●
Torque control is only possible with vector control.
Examples of typical applications in which vector control is used:
●
Hoisting gear and vertical conveyors
●
Winders
●
Extruders