Structure of the SDO protocols
The SDO services use the appropriate protocol depending on the task. The basic structure is
shown below:
n user data
Header information
Byte 0
Byte 1 und 2
Byte 3
Byte 4 ... 7
CS
index sub
index
length
●
The protocol type is contained in byte 0:
–
2F hex: write 4 bytes
–
2B hex: write 3 bytes
–
27 hex: write 2 bytes
–
23 hex: write 1 byte
–
40 hex: read request
–
4F hex: read 4 bytes
–
4B hex: read 3 bytes
–
47 hex: read 2 bytes
–
43 hex: read 1 byte
–
60 hex: write acknowledgment
–
80 hex: error
●
Bytes 1 and 2 contain the index (SINAMICS parameter number)
●
Byte 3 contains the subindex (SINAMICS parameter index)
●
Bytes 4 … 7 contain the data corresponding to the second position of byte 0. In the case
of an error, these bytes contain the abort code