Table 10- 1 General technical data of the CU230P-2
Feature
Data / explanation
6SL3243-0BB30-1CA2:
with CANopen interface
6SL3243-0BB30-1HA2:
with RS485 interface for communication via USS protocol,
BacNet MS/TP and Modbus RTU
Order numbers
6SL3243-0BB30-1PA2:
with PROFIBUS interface
Operating voltage
20.4 V DC … 28.8 V, 1 A
Supply from the Power Module or external via terminals 31 and
32
Power loss
5.0 W
plus power loss of the output voltages
18 V … 30 V (max. 200 mA)
18 V … 30 V (max. 200 mA)
Output voltages
10 V ± 0.5 V (max. 10 mA)
Setpoint resolution
0.01 Hz
Fixed speeds
16
Adjustable
Skip speeds
4
Adjustable
Digital inputs
6 (DI0 … DI5)
Low < 5 V, High > 11 V, maximum input voltage 30 V, current
consumption 5.5 mA, isolated; SIMATIC compatible, PNP/NPN
switchable, reaction time: 10 ms without debounce time (p0724)
Analog inputs
4 (AI0 … AI3)
Differential inputs, 12 bit resolution,
switchable: Current (0 mA … 20 mA) / voltage (0 V … 10 V, -
10 V … + 10 V) / temperature,
response time: 13 ms without debounce time (p0724), AI0 and
AI1 configurable as additional digital inputs: Low < 1.6 V,
High > 4.0 V
Digital outputs / relay
outputs
3 (DO0 … DO2)
DO0 … DO2: 30 V DC 5 A
DO1 additional: 230 V AC, 2 A
update time: 2 ms
Analog outputs
2 (AO0 … AO1)
0 V … 10 V / 0 mA … 20 mA, update time: 4 ms