Technical data
10.2 Technical data, Power Modules
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
307
10.2.1
Technical data, PM230
General data, PM230 - IP55 / UL Type 12
Feature
Version
Line voltage
3-ph. 380 V … 480 V AC ± 10 %
The actual permissible line voltage depends on the installation altitude
Input frequency
47 Hz … 63 Hz
Power factor λ
0.9
Starting current
Smaller than the input current
Permissible short-circuit
current
Frame size A ... C: 42 kA
Frame size D ... F: 65 kA
Pulse frequency (factory
setting)
4 kHz
The pulse frequency can be increased up to 16 kHz in 2 kHz steps. A higher pulse
frequency reduces the permissible output current.
Electromagnetic compatibility
The devices are suitable for environmental classes C1 and C2 in conformance with
IEC 61800-3. For details, see the Hardware Installation Manual, Appendix A2
Braking methods
DC braking
Degree of protection
IP55 / UL Type 12
Degree of protection IP54/ UL Type 12 is reached if an IOP is inserted.
Operating temperature
● without power reduction
● with power reduction
0 °C … +40 °C (32 °F … 104 °F)
to 60° C (140° F)
Storage temperature
-40 °C … +70 °C (-40 °F … 158 °F)
Relative humidity
< 95 % RH - condensation not permissible
Contamination
Protected from contact with dangerous parts, dust, spray water and water jets
Environmental requirements
Protected according to environmental class 3C2 to EN 60721-3-3 against damaging
chemical substances
Shock and vibration
Do not allow the inverter to fall and avoid it being subject to hard shocks. Do not install
the inverter in an area where it could be continuously subject to vibration.
Electromagnetic radiation
Do not install the inverter close to sources of electromagnetic radiation.
Installation altitude
● without power reduction
● with power reduction
Up to 1000 m (3300 ft) above sea level
up to 4000 m (13000 ft) above sea level, for details see the Hardware Installation Manual.
Standards
UL
1)
, CE, C-tick
In order that the system is UL-compliant, UL-certified fuses, overload circuit-breakers or
intrinsically safe motor protection devices must be used.
1)
UL available soon for frame sizes D … F