Configuring the fieldbus
6.3 Communication over CANopen
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
158
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
SDO abort codes
Table 6- 45 SDO abort codes
Abort code
Description
0503 0000h Toggle bit not alternated.
Toggle bit has not changed
0504 0000h
SDO protocol timed out.
Timeout for SDO protocol
0504 0001h
Client/server command specifier not valid or unknown.
Client/server command not valid or unknown
0504 0005h
Out of memory.
Memory overflow
0601 0000h
Unsupported access to an object.
Access to an object that is not supported
0601 0001h
Attempt to read a write only object.
An attempt is made to read a "write-only object"
0601 0002h
Attempt to write a read only object.
An attempt is made to write to a "read-only object"
0602 0000h
Object does not exist in the object dictionary.
Object does not exist in an object dictionary
0604 0041h
Object cannot be mapped to the PDO.
Object cannot be linked with the PDO
0604 0042h
The number and length of the objects to be mapped would exceed PDO length.
The number and length of the objects that are to be linked exceeds the PDO length
0604 0043h
General parameter incompatibility reason.
Basic parameter incompatibility
0604 0047h
General internal incompatibility in the device.
Basic incompatibility in the device
0602 0000h
Object does not exist in the object dictionary.
Object does not exist in an object dictionary
0604 0041h
Object cannot be mapped to the PDO.
Object cannot be linked with the PDO
0604 0042h
The number and length of the objects to be mapped would exceed PDO length.
The number and length of the objects that are to be linked exceeds the PDO length
0604 0043h
General parameter incompatibility reason.
Basic parameter incompatibility
0604 0047h
General internal incompatibility in the device.
Basic incompatibility in the device
0606 0000h
Access failed due to an hardware error.
Access has failed due to a hardware fault
0607 0010h
Data type does not match, length of service parameter does not match.
Data type and length of the service parameter do not match
Summary of Contents for SINAMICS G120 CU230P-2
Page 2: ......