
6-4
Close and Reclose Logic
Date Code 20010625
SEL-311L Instruction Manual
SEL
OGIC
control equation setting 52A is set with optoisolated input IN101. Input IN101 is
connected to a 52a circuit breaker auxiliary contact. When a closed circuit breaker condition is
detected, the CLOSE Relay Word bit is deasserted to logical 0. Setting 52A can handle a 52a or
52b circuit breaker auxiliary contact connected to an optoisolated input (see
Optoisolated Inputs
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
for more 52A setting
examples).
With setting CFD = 60.00 cycles, once the CLOSE Relay Word bit asserts, it remains asserted at
logical 1 no longer than a maximum of 60 cycles. If the Close Failure Timer times out, Relay
Word bit CF asserts to logical 1, forcing the CLOSE Relay Word bit to logical 0 (opening output
103 with the default setting OUT103 = CLOSE).
Defeat the Close Logic
If SEL
OGIC
control equation circuit breaker auxiliary setting 52A is set with numeral 0 (52A =
0), then the close logic is inoperable and the reclosing relay is defeated (see
Reclosing Relay
later in this section). Also, the operation of ground distance elements is delayed by the 3POD
time to reset 3PO.
Circuit Breaker Status
Refer to the bottom of Figure 6.1. Note that SEL
OGIC
control equation setting 52A (circuit
breaker status) is available as Relay Word bit 52A. This makes it convenient to set other
SEL
OGIC
control equations. For example, if the following setting is made:
52A = IN101
(52a auxiliary contact wired to input IN101)
or
52A = !IN101
(52b auxiliary contact wired to input IN101)
then if breaker status is used in other SEL
OGIC
control equations, it can be entered as 52A—the
user doesn’t have to enter IN101 (for a 52a) or !IN101 (for a 52b). For example, refer to
Rotating Default Display
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
. If
circuit breaker status indication is controlled by display point setting DP2:
DP2 = IN101
This can be entered instead as:
DP2 = 52A
(presuming SEL
OGIC
control equation setting 52A = IN101 is made).
Program an Output Contact for Closing
In the factory settings, the resultant of the close logic in Figure 6.1 is routed to output contact
OUT103 with the following SEL
OGIC
control equation:
OUT103 = CLOSE
See
Output Contacts
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
for more
information on programming output contacts.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......