S
ETTINGS
S
HEET
Page 3
OF
30
FOR THE
SEL-311L R
ELAY
(APP = 311L)
Date
R
ELAY
S
ETTINGS
(S
ERIAL
P
ORT
C
OMMAND
SET
AND
F
RONT
P
ANEL
)
Date Code 20011112
Line Parameter Settings (See
Settings Explanations
in
Section 9
)
Positive-sequence line impedance magnitude
(0.05–255.00
W
secondary {5 A nom.};
0.25–1275.00
W
secondary {1 A nom.})
Z1MAG =
Positive-sequence line impedance angle (5.00–90.00 degrees)
Z1ANG =
Zero-sequence line impedance magnitude
(0.05–255.00
W
secondary {5 A nom.};
(0.25–1275.00
W
secondary {1 A nom.})
Z0MAG =
Zero-sequence line impedance angle (5.00–90.00 degrees)
Z0ANG =
Line length (0.10–999.00, unitless)
LL =
Distance Element Zones Enable Settings
Mho phase distance element zones (N, 1–4, 1C–4C) (see Figures 3.26–3.28)
E21P =
Mho ground distance element zones (N, 1–4) (see Figures 3.29–3.31)
E21MG =
Quadrilateral ground distance element zones (N, 1–4)
(see Figures 3.32–3.34)
E21XG =
Instantaneous/Definite-Time Overcurrent Enable Settings
Phase element levels (N, 1–3) (see Figure 3.42)
E50P =
Residual ground element levels (N, 1–4) (see Figure 3.45)
E50G =
Negative-sequence element levels (N, 1–4) (see Figure 3.46)
E50Q =
Time-Overcurrent Enable Settings
Phase element (Y, N) (see Figure 3.47)
E51P =
Residual ground element (Y, N) (see Figure 3.48)
E51G=
Negative-sequence element (Y, N) (see Figure 3.49)
E51Q=
Other Enable Settings
Directional control (Y, AUTO)
(see
Directional Control Settings
in
Section 4
)
E32 =
Out-of-Step (Y, N) (see Figure 3.41)
EOOS =
Load encroachment (Y, N) (see Figure 4.3)
ELOAD =
Switch-onto-fault (Y, N) (see Figure 5.5)
ESOTF =
Voltage elements (Y, N) (see Figures 3.50, 3.51, 3.52, and 3.53)
EVOLT =
Synchronism check (Y, N) (see Figures 3.53 and 3.54)
E25 =
Frequency Elements (N, 1–6)
E81 =
Fault location (Y, N) (see Table 12.1 and
Fault Location
in
Section 12
)
EFLOC =
Loss-of-potential (Y, Y1, N) (see Figure 4.1)
ELOP =
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......