Date Code 20010625
Command Summary
1
SEL-311L Instruction Manual
SEL-311L Relay Command Summary
Access
Level 0
Commands
The only thing that can be done at Access level 0 is to go to Access Level 1. The screen prompt is: =
ACC
Enter Access Level 1. If the main board password jumper is not in place, the relay prompts for entry of
the Access Level 1 password in order to enter Access Level 1.
CAS
Compressed ASCII configuration data
Access
Level 1
Commands
The Access Level 1 commands primarily allow the user to look at information (e.g., settings, metering),
not change it. The screen prompt is: =>
2AC
Enter Access Level 2. If the main board password jumper is not in place, the relay prompts for entry of
the Access Level 2 password in order to enter Access Level 2.
BAC
Enter Breaker Access Level (Access Level B). If the main board password jumper is not in place, the
relay prompts for entry of the Access Level B password.
BRE
Display breaker monitor data (trips, interrupted current, wear).
CEV [n Sx Ly L R C]
Compressed event report (parameters in [ ] are optional)
where:
n
event number (1–41 if LER = 15; 1–22 if LER = 30; 1–11 if LER = 60;
defaults to 1)
S
x
x
samples per cycle (4 or 16); defaults to 4
If S
x
parameter is present, it overrides the L parameter
L
y
y
cycles event report length (1–LER) for filtered event reports, (1–LER + 1) for raw
event reports, defaults to 15 if not specified
L
16 samples per cycle; overridden by the S
x
parameter, if present
R
specifies raw (unfiltered) data; defaults to 16 samples per cycle unless overridden by
the S
x
parameter. Defaults to 16 cycles in length unless overridden with the L
y
parameter.
C
specifies 16 samples per cycle, 15-cycle length
CHIS Compressed
history
COM
p
L
Show a long format communications summary report for all events on M
IRRORED
B
ITS
™ or Differential
Channel
p
.
COM
p n
Show a communications summary for latest
n
events on M
IRRORED
B
ITS
or Differential Channel
p
.
COM
p m n
Show a communications summary report for events
n
through
m
on M
IRRORED
B
ITS
or Differential
Channel
p
.
COM
p d1
Show a communications summary report for events occurring on date
d1
on M
IRRORED
B
ITS
or
Differential Channel
p
.
COM
p d1 d2
Show a communications summary report for events occurring between dates
d1
and
d2
on M
IRRORED
B
ITS
or Differential Channel
p
. Entry of dates is dependent on the Date Format setting DATE_F
(= MDY or YMD).
COM C
p
Clears the communications summary report for Channel
p
.
CST
Compressed status report
CSU
Compressed event summary
DAT
Set / Show relay date.
DAT m/d/y
Enter date in this manner if Date Format setting DATE_F = MDY.
DAT y/m/d
Enter date in this manner if Date Format setting DATE_F = YMD.
DNP
Set / Show DNP map
EVE
n
Show event report number
n
with 1/4-cycle resolution.
EVE L
n
Show event report number
n
with 1/16-cycle resolution.
EVE R
n
Show raw event report number
n
with 1/16-cycle resolution.
EVE B
n
Show event report number
n
for backup elements (not including differential).
EVE C
n
Show compressed event report number
n
for use with SEL-5601 Analytic Assistant.
GRO
Display active group number.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......