Trip and Target Logic
Date Code 20010625
SEL-311L Instruction Manual
Logic Outputs
The following logic outputs can be tested by assigning them to output contacts. See
Output
Contacts
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
for more information
on output contacts.
UBB1, UBB2—Unblocking Block Output(s)
In two-terminal line DCUB applications (setting ECOMM = DCUB1), UBB1 disables tripping if
the loss-of-channel condition continues for longer than time UBDURD.
In three-terminal line DCUB applications (setting ECOMM = DCUB2), UBB1 or UBB2 disable
tripping if the loss-of-channel condition (for the respective Channel 1 or 2) continues for longer
than time UBDURD.
The UBB1 and UBB2 are routed in various combinations in Figure 5.13 to control Relay Word
bit UBB, depending on enable setting ECOMM = DCUB1 or DCUB2. Relay Word bit UBB is
the unblock block input into the trip logic in Figure 5.4. When UBB asserts to logical 1, tripping
is blocked.