5-6
Trip and Target Logic
Date Code 20010625
SEL-311L Instruction Manual
More than one trip setting (or all four trip settings TRCOMM, DTT, TRSOTF, and TR) can be
set. For example, in a communications-assisted trip scheme, TRCOMM is set with direction
forward overreaching Zone 2 distance elements, TR is set with direction forward underreaching
Zone 1 distance elements and other time delayed elements (e.g., Zone 2 definite-time distance
elements), and TRSOTF is set with instantaneous directional and non-directional elements.
Figure 5.4: Trip Logic
In addition, when setting EHST
r
1, Relay Word bit TRIP asserts when any 87L element detects
an internal fault.