B-4
Firmware Upgrade Instructions
Date Code 20011112
SEL-311L Instruction Manual
12.
The relay illuminates the EN front-panel LED if the original relay settings were retained
through the download. If the EN LED is illuminated, proceed to Step 13; otherwise, the
relay may display various self-test failures because of changes in the way memory is
used.
Press
<ENTER>
to see if the Level 0 prompt “=” appears on your terminal screen. If
the relay does not display the Level 0 prompt, the Relay baud rate has changed back to
the factory default of 2400 baud; go to self-test failure: CR_RAM and EEPROM, Step
12a. If the relay does display the Level 0 prompt, go to Step 12b.
Self-test failure: CR_RAM and EEPROM
a. Set your communications software settings to 2400 baud, 8 data bits, 1 stop
bit. Now enter Access Level 2 by issuing the
ACC
and
2AC
commands, (the
factory default passwords will be in effect: OTTER for level 1, TAIL for
level 2).
b. Issue the Restore Settings (
R_S
) command to restore the factory default
settings in the relay. This takes about two minutes, then the EN LED will
illuminate.
Note:
If the relay asks for a part number to be entered, use the number from
the label on the firmware diskette, or from the new part number sticker
(if supplied).
c. Enter Access Level 2 by issuing the
ACC
and
2AC
commands, (the factory
default passwords will be in effect: OTTER for level 1, TAIL for level 2).
d. Restore the original settings as necessary, using the SEL-5010 Settings
Assistant, or with each of the following commands:
SET G
,
SET 1
,
SET L 1
,
SET 2
,
SET L 2
,
SET 3
,
SET L 3
,
SET 4
,
SET L 4
,
SET 5
,
SET L 5
,
SET 6
,
SET L 6
,
SET P 1
,
SET P 2
,
SET P 3
,
SET P F
,
SET R
,
SET X
,
SET Y
.
e. Set the original relay passwords saved in Step 3 via the
PAS
command.
For
example,
PAS 1:APPLE <ENTER>
sets the level 1 password to APPLE.
Use a similar format for
PAS B
and
PAS 2
. The
PAS
command is case-
sensitive, so the lower and upper case letters are treated differently.
If there are still any FAIL codes on the Relay LCD, see
Section 13: Testing,
Troubleshooting, and Commissioning.
13. Verify the calibration settings by issuing the
SHO C
command. If the settings do not
match the settings recorded in Step 3, reissue the settings with the
SET C
command.
14. Issue the Version (
VER
) command and check the part number from the label on the
firmware diskette against the part number on the screen. If they match, go to Step 15;
otherwise, type
PAR <ENTER>
and type the number from the diskette label and press
<ENTER>
. If the relay reinitializes after saving the changes, go to Access Level 2.
15. Execute the Status (
STA
) command to verify that all relay self-test parameters are
within tolerance, and that the relay is enabled.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......