7-16
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20010625
SEL-311L Instruction Manual
Figure 7.14: Latch Control Switch Operation Time Line
Use a Remote Bit Instead to Enable/Disable the Reclosing Relay
Use a remote bit to enable/disable the reclosing relay, instead of an optoisolated input. For
example, substitute remote bit RB1 for optoisolated input IN104 in the settings accompanying
Figure 7.13:
SET1 = /RB1 * !LT1
[= (rising edge of remote bit RB1) AND NOT(LT1)]
RST1 = /RB1 * LT1
[= (rising edge of remote bit RB1) AND LT1]
79DTL = !LT1
[= NOT(LT1); drive-to-lockout setting]
Pulse remote bit RB1 to enable reclosing, pulse remote bit RB1 to disable reclosing, etc.—much
like the operation of optoisolated input IN104 in the previous example. Remote bits (Relay
Word bits RB1 through RB16) are operated through the serial port. See Figure 7.9 and
Section 10: Line Current Differential Communications and Serial Port Communications and
Commands
for more information on remote bits.
These are just a few control logic examples—many variations are possible.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......