Date Code 20010625
Trip and Target Logic
5-9
SEL-311L Instruction Manual
Set Trip
In SEL
OGIC
control equation setting TR = M1P + Z1G + M2PT + Z2GT + 51GT + 51QT + OC:
v
Distance elements M1P, M2PT, Z1G, and Z2GT and time-overcurrent elements 51GT
and 51QT trip directly. Time-overcurrent and definite-time overcurrent elements can be
torque controlled (e.g., elements 51GT and 51QT are torque controlled by SEL
OGIC
control equation settings 51GTC and 51QTC, respectively). Check torque control
settings to see if any control is applied to time-overcurrent and definite-time overcurrent
elements. Such control is not apparent by mere inspection of trip setting TR or any
other SEL
OGIC
control equation trip setting.
v
Relay Word bit OC asserts for execution of the OPEN Command. See
OPE Command
(Open Breaker)
in
Section 10: Line Current Differential Communications and Serial
Port Communications and Commands
for more information on the OPEN Command.
With setting TDURD = 9.000 cycles, once the TRIP Relay Word bit asserts via SEL
OGIC
control
equation setting TR, it remains asserted at logical 1 for a minimum of 9 cycles.
Unlatch Trip
In SEL
OGIC
control equation setting ULTR =!(50L + 51G):
Both elements must be deasserted before the trip logic unlatches and the TRIP Relay Word
bit deasserts to logical 0.
Additional Settings Examples
The factory setting for SEL
OGIC
control equation setting ULTR is a trip element unlatch
condition. A circuit breaker status unlatch trip condition can be programmed as shown in the
following examples.
Unlatch Trip with 52a Circuit Breaker Auxiliary Contact
A 52a circuit breaker auxiliary contact is wired to optoisolated input IN101.
52A =
IN101
(SEL
OGIC
control equation circuit breaker status setting—see
Optoisolated Inputs
in
Section 7: Inputs, Outputs, Timers, and
Other Control Logic
)
ULTR = !52A
Input IN101 has to be deenergized (52a circuit breaker auxiliary contact has to be open) before
the trip logic unlatches and the TRIP Relay Word bit deasserts to logical 0.
ULTR = !52A = NOT(52A)
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......