9-36
Setting the Relay
Date Code 20010625
SEL-311L Instruction Manual
Line Settings (Only Applicable if Potentials Are Available)
Line impedance settings Z1MAG, Z1ANG, Z0MAG, and Z0ANG are used in distance relaying,
fault locator (see
Fault Location
in
Section 12: Standard Event Reports and SER
) and in
automatically making directional element settings Z2F, Z2R, Z0F, and Z0R (see
Settings Made
Automatically
in
Section 4: Loss-of-Potential Logic, CCVT Transient Detection,
Load-Encroachment, and Directional Element Logic
). A corresponding line length setting (LL)
is also used in the fault locator.
The line impedance settings Z1MAG, Z1ANG, Z0MAG, and Z0ANG are set in
Ω
secondary. To
convert line impedance (
Ω
primary) to
Ω
secondary:
Ω
primary • (CTR/PTR) =
Ω
secondary
where:
CTR = phase (IA, IB, IC) current transformer ratio
PTR = phase (VA, VB, VC) potential transformer ratio (wye-connected)
Line length setting LL is unitless and corresponds to the line impedance settings. For example, if
a particular line length is 15 miles, enter the line impedance values (
Ω
secondary) and then enter
the corresponding line length:
LL
=
15.00
(miles)
If the same length of line is measured in kilometers rather than miles, then enter:
LL
=
24.14
(kilometers)
Enable Settings
The enable settings (E87L through EBMON) control the setting subgroups that follow. For
example, setting EBMON = Y will enable the breaker monitor settings that immediately follow it.
Hence, the enable settings are used to limit the number of settings that need to be made.
Other System Parameters
The global settings NFREQ and PHROT allow you to configure the SEL-311L Relay to your
specific system.
Set NFREQ equal to your nominal power system frequency, either 50 Hz or 60 Hz.
Set PHROT equal to your power system phase rotation, either ABC or ACB.
Set DATE_F to format the date displayed in relay reports and the front-panel display. Set
DATE_F to MDY to display dates in Month/Day/Year format; set DATE_F to YMD to display
dates in Year/Month/Day format.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......