3-42
Line Current Differential, Distance, Out-of-Step, Overcurrent,
Date Code 20011112
Voltage, Synchronism Check, and Frequency Elements
SEL-311L Instruction Manual
|IA|
50L2
(Advanced Setting)
From Figure 4.12 32GF
_
+
_
+
|IG|
50GZ2
(Advanced Setting)
See Note 1 mAG < Z2MG
M311L120
FSA
From Figure 5.5 3PO
From Figure 4.1 ILOP
VPOLV
MAG2
MBG2
MCG2
XAG2
XBG2
XCG2
Z2G
Zone 2 A-Phase Mho Ground Distance Logic.
B and C Phase Are Similar.
Note 1: mAG = A-Phase to Ground Distance Calculation
Z2MG = Zone 2 Distance Setting
Relay
Word
Bits
Relay
Word
Bit
Relay
Word
Bits
(unless
noted)
Figure 3.33: Zone 2 Mho Ground Distance Logic
DIR
n = F (Setting)
From Figure 4.12 32GF
|IA|
50L
n
(Advanced Setting)
mAG < Z
nMG
FSA
From Figure 5.5 3PO
From Figure 4.1 ILOP
VPOLV
_
+
Zone 3 and 4 A-Phase Mho Ground Distance Logic.
B- and C-Phase Logic Is Similar.
Note 1: mAG = A-Phase to Ground Distance Calculation
Z
nMG = Zone n Distance Setting
n = 3 for Zone 3
n = 4 for Zone 4
DWG: M311L121
From Figure 4.12 32GR
_
+
|IG|
50GZ
n
(Advanced Setting)
MAG
n
MBG
n
MCG
n
XAG
n
XBG
n
XCG
n
Z
nG
mAG > -Z
nMG
See Note 1
Relay
Word
Bit
Relay
Word
Bits
Relay
Word
Bits
(unless
noted)
Figure 3.34: Zones 3 and 4 Mho Ground Distance Logic
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......