Date Code 20010625
Inputs, Outputs, Timers, and Other Control Logic
7-45
SEL-311L Instruction Manual
Make corresponding, complementary text settings:
DP1_1 = 79 ENABLED
DP1_0 = 79 DISABLED
Display point setting DP1 controls the display of the text settings.
Reclosing Relay Enabled
In Figure 7.32, optoisolated input IN102 is energized to enable the reclosing relay, resulting in:
DP1 = IN102 = logical 1
This results in the display of corresponding text setting DP1_1 on the front-panel display:
&/"#-&%
Reclosing Relay Disabled
In Figure 7.32, optoisolated input IN102 is deenergized to disable the reclosing relay, resulting
in:
DP1 = IN102 = logical 0
This results in the display of corresponding text setting DP1_0 on the front-panel display:
%*4"#-&%
Circuit Breaker Status Indication
Make SEL
OGIC
control equation display point setting DP2:
DP2 = IN101
Make corresponding, complementary text settings:
DP2_1 = BREAKER CLOSED
DP2_0 = BREAKER OPEN
Display point setting DP2 controls the display of the text settings.
Circuit Breaker Closed
In Figure 7.32, optoisolated input IN101 is energized when the 52a circuit breaker auxiliary
contact is closed, resulting in:
DP2 = IN101 = logical 1
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......