9-44
Setting the Relay
Date Code 20010625
SEL-311L Instruction Manual
800
4584.6
1 • 10
3
100
10
1
0.1
0.01
100
1 • 10
3
1 • 10
4
Time
(sec
on
ds)
T51P Overcurrent Protection
Transformer Overcurrent Protection
Primary Amps
Lowest Phase
Differential Current
T51PT
Load Transformer
Primary Overcurrent
Protection
609.8
Max. Load
Transformer
Secondary Fault
Current
T50P
M311L139
Time delay (OFF, 0.00–16000.00 cycles)
T50PD = OFF
No time delay is needed since the tapped load phase instantaneous overcurrent element does not
see faults on the load transformer secondary.
Tapped-Load Residual Ground Time-Overcurrent Element Settings (If ETG = Y)
Pickup (OFF, 0.50–16.00 A secondary)
T51GP = 2.0
Since the transformers are connected delta-wye and T51G is a differential element, T51G only
asserts for faults on the transmission line.
Set the T51GP = 2.0 A to detect a high resistance ground fault on the transmission line.
(V secondary / T51GP) • (CTR / PTR) = (66.4 / 2.0 )• (2000 / 240) = 276.7 Ohms Primary
Curve (U1–U5; C1–C5)
T51GC = U3
Time dial (0.50–15.00 for curves U1–U5; 0.05–1.00 for curves C1–C5)
T51GTD = 1.00
Electromechanical reset delay (Y, N)
T51GRS = Y
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......