Date Code 20010625
Loss-of-Potential, CCVT Transient Detection,
4-21
Load-Encroachment, and Directional Element Logic
SEL-311L Instruction Manual
Figure 4.15: Positive-Sequence Voltage-Polarized Directional Element for Phase Distance
Elements
D
IRECTIONAL
C
ONTROL
S
ETTINGS
The directional control for overcurrent elements is configured by making directional control
enable setting E32. Setting E32 has setting choices:
Y
All directional control settings made manually
AUTO Sets most of the directional element settings automatically
Settings Made Automatically
If the directional control enable setting E32 is set:
E32 = AUTO
then the following directional control settings are calculated and set automatically:
Z2F, Z2R, 50QFP, 50QRP, a2, k2, 50GFP, 50GRP, a0, Z0F, and Z0R
Once these settings are calculated automatically, they can only be modified if the user goes back
and changes the directional control enable setting to E32 = Y.
The remaining directional control settings are not set automatically if setting E32 = AUTO. They
have to be set by the user, whether setting E32 = AUTO or Y. These settings are:
DIR3, DIR4, ORDER, and E32IV
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......