Date Code 20010625
Loss-of-Potential, CCVT Transient Detection,
4-25
Load-Encroachment, and Directional Element Logic
SEL-311L Instruction Manual
a2 Set Automatically
If configuration setting E32 = AUTO, setting a2 is set automatically at:
a2 = 0.1
For setting a2 = 0.1, the negative-sequence current (I
2
) magnitude has to be greater than 1/10 of
the positive-sequence current (I
1
) magnitude in order for the negative-sequence voltage-polarized
directional elements to be enabled (
,
,
).
k2—Zero-Sequence Current Restraint Factor, |I
2
|/|I
0
|
Setting Range:
0.10–1.20 (unitless)
Note the directional enable logic outputs in Figure 4.6:
32QE
enable for the negative-sequence voltage-polarized directional element that
controls the phase distance and negative-sequence overcurrent elements
32QGE enable for the negative-sequence voltage-polarized directional element that
controls the ground distance and residual ground overcurrent elements
The k2 factor is applied to enable 32QGE. The negative-sequence current (I
2
) magnitude has to
be greater than the zero-sequence current (I
0
) magnitude multiplied by k2 in order for the 32QGE
enable (and following negative-sequence voltage-polarized directional element in Figure 4.9) to
be enabled:
,
N
,
This check assures that the relay uses the most robust analog quantities in making directional
decisions for the ground distance and residual ground overcurrent elements.
If both of the internal enables:
32VE
enable for the zero-sequence voltage-polarized directional element that controls
the ground distance and residual ground overcurrent elements
32IE
enable for the channel IP current-polarized directional element that controls the
ground distance and residual ground overcurrent elements
are deasserted, then factor k2 is ignored as a logic enable for the 32QGE enable. If neither the
zero-sequence voltage-polarized nor the channel IP current-polarized directional elements are
operable, fewer restrictions (i.e., factor k2) are put on the operation of the negative-sequence
voltage-polarized directional element.
k2 Set Automatically
If configuration setting E32 = AUTO, setting k2 is set automatically at:
k2 = 0.2
For setting k2 = 0.2, the negative-sequence current (I
2
) magnitude has to be greater than 1/5 of the
zero-sequence current (I
0
) magnitude in order for the negative-sequence voltage-polarized
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......