10-34
Line Current Differential Communications
Date Code 20010625
and Serial Port Communications and Commands
SEL-311L Instruction Manual
sequence current plots in the operating characteristic. Both the vector sum and Alpha plane
values can be used to evaluate the quality of the protection elements.
A typical display of
MET
data follows. Note that currents are displayed in primary values while
settings are in secondary values. In this case Channel Y is a standby channel. Channel X is used
for calculated values.
=>MET <ENTER>
SEL-311L Date: 06/05/01 Time: 10:28:50.360
EXAMPLE: BUS B, BREAKER 3
Local A B C 3I0 3I2 I1
I MAG (A Pri) 386.444 385.401 385.597 2.838 1.747 385.813
I ANG (DEG) -0.10 -119.90 119.80 -2.60 -19.00 0.00
Channel X PRIM A B C 3I0 3I2 I1
I MAG (A Pri) 385.644 387.077 395.563 32.567 30.969 389.172
I ANG (DEG) 179.60 59.50 -56.10 14.80 133.70 -179.00
Channel Y STBY A B C 3I0 3I2 I1
I MAG (A Pri) 386.082 385.349 395.433 31.476 32.077 388.685
I ANG (DEG) 179.70 59.80 -55.70 15.20 136.40 -178.70
Vector Sum A B C 3I0 3I2 I1
I MAG (A Pri) 2.173 4.378 29.665 35.285 29.427 7.551
I ANG (DEG) 68.10 -7.60 12.20 13.40 132.10 -115.90
Alpha Plane A B C ZERO-SEQ NEG-SEQ POS-SEQ
RADIUS 0.990 1.000 1.020 0.000 0.000 1.000
ANG (DEG) 179.60 179.40 175.80 0.00 0.00 178.90
=>
MET B
k
—Instantaneous Metering
The
MET B
commands provide access to the local relay metering data. Metered quantities
include phase voltages and currents, sequence component voltages and currents, power,
frequency, substation battery voltage, energy, demand, and maximum/minimum logging of
selected quantities. To make the extensive amount of meter information manageable, the relay
divides the displayed information into five groups: Instantaneous Differential, Instantaneous
Backup, Demand, Energy, and Maximum/Minimum.
The
MET B
k
command displays instantaneous magnitudes (and angles if applicable) of the
following quantities:
Currents I
A,B,C,P
I
G
Input currents (A primary)
Residual ground current (A primary; I
G
= 3I
0
= I
A
+ I
B
+ I
C
)
Voltages V
A,B,C,S
Wye-connected voltage inputs (kV primary)
Power MW
A,B,C
MW
3P
MVAR
A,B,C
MVAR
3P
Single-phase megawatts
Three-phase megawatts
Single- and three-phase megavars
Three-phase megavars
Power Factor
PF
A,B,C,3P
Single- and three-phase power factor; leading or lagging
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......