6-2
Close and Reclose Logic
Date Code 20010625
SEL-311L Instruction Manual
See the settings sheet in
Section 9: Setting the Relay
for setting ranges.
Figure 6.1: Close Logic
Set Close
If all the following are true:
•
The unlatch close condition is not asserted (ULCL = logical 0).
•
The circuit breaker is open (52A = logical 0).
•
The reclose initiation condition (79RI) is not making a rising edge (logical 0 to logical
1) transition.
•
And a close failure condition does not exist (Relay Word bit CF = 0).
Then the CLOSE Relay Word bit can be asserted to logical 1 if either of the following occurs:
•
A reclosing relay open interval times out (qualified by SEL
OGIC
control equation
setting 79CLS—see Figure 6.2).
•
Or SEL
OGIC
control equation setting CL goes from logical 0 to logical 1 (rising edge
transition).
The CLOSE command is the only value in the close logic in the factory default settings:
CL = CC
Relay Word bit CC asserts for execution of the CLOSE Command. See
CLO Command (Close
Breaker)
in
Section 10: Line Current Differential Communications and Serial Port
Communications and Commands
for more information on the CLOSE Command. More
discussion follows later on the factory settings for setting CL.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......