5-62
5.10 Group 9: Communication Parameter
09-00
Communication Address
Factory setting
1
Settings
1-254
1
When the system is controlling or monitoring with the RS-485 series connection
communication interface, every drive has to be determined with one communication
address then and that the address connected to the network should be specific and
could not be repeated.
09-01
Transmission Speed of the Communication
Factory setting
9.6
Settings
4.8~115.2
Kbits/s
1
Through the internal RS-485 series connection ports within the computer, users are to
set and revise the parameters within the drive, and to control the operation of the drive,
and further, to monitor the operation status of the drive. This parameter is utilized in
setting up the transmission speed between the computer and the drive.
09-02
Transmission Fault Treatment
Factory setting
3
Settings
0 warn and keep operating
1 warn and RAMP to stop
2 warn and COAST to stop
3 no treatment and no display
1
This parameter is utilized in setting the drive’s treatment toward transmission overtime fault
(e.g. when the communication cord is broken) during the communication.
09-03
Overtime Detection
Factory setting
0
Settings
0
disabled
1~100s
1
This parameter is utilized in setting the transmission overtime between the
communication and the keypad.
09-04
Communication Protocol
Factory setting
0
Settings
0 to 17
Settings
Function
Settings
Function
0
7, N, 1 for ASCII
9
8, O, 1 for ASCII
1
7, N, 2 for ASCII
10
8, E, 2 for ASCII
2
7, E, 1 for ASCII
11
8, O, 2 for ASCII