4-22
Group 6: Protection Parameter
Parameters
Functions
Settings
Factory
Setting
Customer
06-00
Low Voltage Level
160~220V
320-440V
180
360
06-01
Over-Voltage Stall
Prevention 700.0~900.0V
760.0
06-02
Phase-Loss
Protection
0: warn and keep operating
1: warn and ramp to stop
2: warn and coast to stop
0
06-03
Over-Current Stall
Prevention during
Acceleration
20~250%
170
06-04
Over-Current Stall
Prevention during
Operation
20~250%
170
06-05
Over-Current Deceleration
Time during Operation
0.05~600.00 s
3.00
06-06
Over-Torque Detection
Selection (oL2)
0: disabled
1: Over-torque detection
during constant speed
operation, continue to
operate after detection.
2: Over-torque detection
during constant speed
operation, stop operation
after detection.
3: Over-torque detection
during entire (acceleration,
steady state, deceleration)
operation, continue
operation after detection.
4: Over-torque detection
during entire (acceleration,
steady state, deceleration)
operation, stop operation
after detection.
0
06-07
Over-Torque Detection
Level (oL2)
10~250%
150
06-08
Over-Torque Detection
Time (oL2)
0.0~60.0 s
0.1