4-25
Group 7: Special Parameter
Parameters
Functions
Settings
Factory
Setting
Customer
07-00
Software Braking Level
700.0~900.0V
760.0
07-01
DC Braking Current Level
0~100%
0
07-02
DC Braking Time at Start-up
0.00~60.00 s
0.00
07-03
DC Braking Time during a
STOP
0.00~60.00 s
0.00
07-04
Frequency point for DC
Braking
0.00~400.00Hz
0.00
07-05
Increasing Rate of the DC
Voltage
1~500
30
07-06
Re-activate after Momentary
Power Loss
0: disable
1: begins from command
frequency
2: begins from minimum
output frequency
0
07-07
Maximum Allowable Power
Loss Time
0.1~5.0 s
2.0
07-08
Base Block Time for Speed
Search
0.1~5.0 s
0.5
07-09
Maximum Current Level for
Speed Search
20~200%
150
07-10
Deceleration Time for Speed
Search
0.50~600.00 s
3.00
07-11
Auto Restart after Fault
0~10
0
07-12
Speed
Search
Type
0: speed search disabled
1: speed search through
the frequency command
2: FWD-speed search only
(motor only runs in FWD
direction)
3: REV-speed search only
(motor only runs in REV
direction)
4: FWD/REV speed search
enabled in both
directions (fwd first)
5: REV/FWD speed search
enabled in both
directions (rev first)
0
07-13
Speed Search Frequency
(FWD direction)
0.00~400.00Hz
60.00/
50.00
07-14
Speed Search Frequency
(REV direction)
0.00~400.00Hz
60.00/
50.00
07-15
Gear Gap
Acceleration-Interruption Time
0.00~400.00 s
0.00