5-4
44 torque limit (Pr. 06-12)
45 the q axis current (V/F and vector)
46 Frequency of Encoder (Channel 1)
49 PID error value
51 AVI input voltage
52 ACI input current
53 AUI input voltage
55 Auxiliary frequency value
60 Input state of digital terminals
61 Output state of digital terminals
84 Input frequency of pulse (Channel 2) 85 Input position of pulse (Channel 2)
86 OL3
timer
1
This parameter defines the display content the User Defined setting. The User Defined
setting may be displayed upon power up (Pr. 00-03) or by pressing the Mode key on the
keypad and scrolling until the “U” is illuminated.
00-05
User-Defined Coefficient Setting
Factory setting 0
Settings
4 digit
0-3: the number of the decimal places
3-0
digit
40~9999
1
This parameter allows the user to define a special value relative to the output frequency.
4th digit: Setting of the decimal places; 0 means that there is no decimal place and
3
stands for three decimal places.
3~0 digit: The actual value the maximum output frequency should correspond to.
1
Example: To display rpm’s for a 4-pole 60Hz motor with a base speed 1800rpm and no
slip, Pr 00-05 must be set as follows.
Set the 4
th
bit = 0, 3
rd
bit = 1, 2
nd
bit = 8, 1
st
bit = 0, 0 bit = 0.
The result of setting 01800 in Pr. 00-05 determines the value at 60Hz (Maximum Output
Frequency).
1
After this parameter is set, all functions relative to the frequency (except for the V/F
Curve frequency parameters) will automatically be changed to an RPM sale. RPM,
instead of Hz, will now be the unit for the keypad, and thus, if it is displayed as 60.00
before the setup, it will now display 1800 after the setup. Other parameters such as the
multi-step speed and JOG will be automatically changed also.
00-06
Software Version
Settings
Read-only
00-07
Password Input
Factory setting 0
Settings
0~9999
00-08
Password Setting
Factory setting 0
Settings
0~9999