5-25
This function uses the Bit setting method.
Example: If Pr.02-10 is 1 1AC Drive running), and Relay 1 is set to N.O., then R1 close when
the drive has an output and will open when the drive has stopped.
Settings
Bit
content
Relay 1
03-07
Relay 2
03-08
MO1
03-09
MO2
03-10
0
0000
N.O.
N.O.
N.O.
N.O.
1
0001
N.O.
N.O.
N.O.
N.C.
2
0010
N.O.
N.O.
N.C.
N.O.
3
0011
N.O.
N.O.
N.C.
N.C.
4
0100
N.O.
N.C.
N.O.
N.O.
5
0101
N.O.
N.C.
N.O.
N.C.
6
0110
N.O.
N.C.
N.C.
N.O.
7
0111
N.O.
N.C.
N.C.
N.C.
8
1000
N.C.
N.O.
N.O.
N.O.
9
1001
N.C.
N.O.
N.O.
N.C.
10
1010
N.C.
N.O.
N.C.
N.O.
11
1011
N.C.
N.O.
N.C.
N.C.
12
1100
N.C.
N.C.
N.O.
N.O.
13
1101
N.C.
N.C.
N.O.
N.C.
14
1110
N.C.
N.C.
N.C.
N.O.
15
1111
N.C.
N.C.
N.C.
N.C.
Note: N.O. : normal open, N.C.: normal close
02-16
Counter Values Achieve the Pre-Set Values
Factory setting 0
Settings
0~65500
1
The input contact of the counter could set the multi-function terminal MI6 (with the
designated terminal Pr. 02-06 as 26) as the trigger terminal, and when the counting is over
(which reaches the destination), the signals could select one among the multi-function
output terminals (with Pr. 02-10~02-13 set as 21) to be the motion contact.
02-17
Designated Counter Value Achieved
Factory setting 0
Settings
0~65500
1
When the counter value starts counting upward from 1 to the setting of this parameter, its
corresponding multi-function output terminal contact with the “arbitrary counting
achieves the output indication” function would start functioning. This parameter could
be utilized at the moment when the counting is almost to an end, and then, set the
output signal to enable the drive operating at a low speed till it stopped.
Summary of Contents for S3000 Series
Page 8: ...2 5 DIMENTIONS 2 5...
Page 9: ...2 6 403 216...
Page 10: ...2 7...
Page 11: ...2 8 S3000 IP06...