This parameter determines the frequency point of DC braking for both Pr. 07-02 and Pr.
07-03.
1
During deceleration, the drive will begin to output a DC current once the frequency reaches
the value set in this parameter.
1
Immediately following a RUN command, the drive will output a DC current until the output
frequency reaches the value set in this parameter.
1
The DC braking is commonly used to help decrease the deceleration time. For the best
stopping performance, it is recommended to use the Deceleration Time (Pr.01-13) to slow
the motor and then apply the DC brake at speeds below 25hz.
07-05
Increasing Rate of the DC Voltage
Factory setting
30
Settings
1~500
1
This parameter determines the rate of increase for the DC voltage output during the DC
injection braking function.
07-06
Re-activate after Momentary Power Loss
Factory setting
0
Settings
0 disable
1 begins from command frequency
2 begins from minimum output frequency
1
This parameter selects the speed search type after a momentary power loss.
07-07
Maximum Allowable Power Loss Time
Factory setting
2.0
Settings
0.1~5.0 s
Output Frequency
Time
ON
OFF
RUN/STOP
Startup Frequency
01-09